UL 489 Mira MCCB,3 Pole, L/L Lug,480V 35kA |
|
Description:
|
|
LL EXP
|
|
|
Specifications
|
|
Frame Size
|
125AF
|
|
Rated Current (A)
|
15,20,30,40,50,60,80,100,125
|
|
Number of poles
|
3
|
|
Rated operational voltage, UeAC
|
600V
|
|
UL interrupting rating (kA)
|
|
AC 50/60Hz, 240V
|
50
|
|
AC 50/60Hz, 480V
|
35
|
|
AC 50/60Hz, 600V
|
10
|
|
Mechanical life (operations)
|
4000
|
|
Electrical life @ 600VAC (operations)
|
4000
|
|
Weight (lbs)
|
2.64
|
|
Dimensions (in.) W x H x D
|
3.54 x 6.46 x 3.39
|
|
Ampere rating
|
80A
|
|
Thermal trip setting
|
64-80A
|
List prices shown unless signed in as Cerus Trade Account. For qualified trade pricing, please contact us at 800-962-3787. Oregon has no sales tax.
|
|
|
|
| Product No.: |
TD125NU FMU 125 80A |
| Price: |
$ 367.00 |
|
|
|
|
|
|
|
|
Characteristics
|
|
|
High Interrupting Capacity
|
|
|
• Variety of trip units available.
|
|
|
• UL 489 and IEC standards.
|
|
|
• Four frame sizes from 15 through 800Amp.
|
|
|
• Common mounting depths between frames 15-800.
|
|
|
|
Advanced Performance
|
|
|
• Accessories mount on right or left side to simplify panel wiring.
|
|
|
• Standardized accessories are interchangeable on all models and are field or factory installed.
|
|
|
• Advanced arc quenching technology enables excellent trip performance and long life.
|
|
|
|
|
|
|